Connection   Type 4 wire, 3 element (3p4w)
Voltage Direct, with piercing insulated connectors (10, 150mm²)
Current Rogowski coils with open loop (opening diameter 50 - 200mm)
Voltage Nominal working voltage 3x230/400 V
Working voltage range 0.5 * Un ... 1.15 * Un
Nominal frequency 50 Hz
Current*    Nominal current, In 40A; 200A
Max current, Imax 400A; 2000A*
Min current, Imin 0.05 * In
Starting current, Ist 0.002 * In *Adjustable range
 Registered parameters  Voltage  RMS, max instantaneous value, sag / swell, frequency
 Current  RMS, max instantaneous value, overload
 Active power  By phase, total
 Apparent power  By phase, total
 Power factor  Absolute value, sign, inductive / capacitive
 Active energy  By phase, total, direction, load profile
 Conformity  Certification  CE, UL 61010-1 (Rogowski coils)
 Precision class  B (according to EN 50470-3)
 UV resistance  According to material UL recognition files
 Intrinsic consumption   Voltage circuits  10 VA
 Current circuits  -
 Data transfer   Interface  GSM / GPRS
 Data type  Measurements, time synchronisation, diagnostic / configuration SMS
 Physical       Dimensions (LxWxH)  225 x 85 x 68 mm
 Weight  420 g
 Mounting  On 35 mm DIN rail
 Enclosure  Polycarbonate plastic, UL94-V0
 External connections  Connector for U cable, 3 connectors for Rogowski coils
 Cable length  2 - 5 m
 Operating conditions  IP protection class  IP67 (device case, connectors, Rogowski coils)
 Work temperature   -40°C to +70°C
 -40°C to +55°C (with built-in Li-ion battery)

There are 6 available device configurations depending on your voltage and current measurement needs

Voltage connection
Current connection

 

Installation is possible outdoors regardless of temperature and weather

Sun
Rain
Snow

 

Key installation aspects in comparison:

Traditionally
Our approach
Installation process takes at least 2 hours
Set up in 15 minutes
Power supply must be disconnected
Power supply doesn't have to be disconnected
Electrical installation is modified (wires to be cut)
Electrical installation doesn't have to be modified
Readings are taken from time to time
Complete data analysis available on-line

Voltage connection examples:

Office building in Riga

Production plant in Olaine

The device with a display offers functionality expanded with vector diagrams and voltage harmonics

 

Current vector guideline
Neutral current vector
Phase voltages
Phase currents
Angle between voltage and current vectors
Line voltages
Current vector scale
Voltage vector scale
Current in neutral
Current measurement range

The GRIDLINK accessory device conveniently and quickly enables the system to determine the status of fuses in transformer stations. For example, you can instantly see that there are no problems with wiring, but an outgoing line to the factory or a household has a broken fuse

 

       
Combination with GRIDLINK, using PowerLine Monitoring of max 15 outgoing connections IP67 body

 